Ok so Jon checked it out and I had 1.2A on one side and 1.3A on the other. He said that wasn't leakage but that the two poles weren't sharing the load equally. He couldn't say why that was but he felt that it wasn't the VFD's from the pumps causing an issue. But the difference was enough to be tripping the GFCI. Why it only recently started, who knows. So we pulled the expensive GFCI breaker out and slapped a 2 pole in and so far so good *knock on computer*.